Description

Any occupied room requires the correct supply of fresh air and, at the same time, the control of the internal thermo-hygrometric conditions, through the recovery of energy from the air extracted from the room, by means of static counter-flow heat recoveries, the level of well-being of the occupants is guaranteed, both in summer and winter. For buildings that require air changes and are not equipped with dedicated air conditioning systems, the installation of such units allows the supply of primary air at controlled temperature without substantially changing the internal conditions in the occupied spaces. These units also make it possible to guarantee support for the air conditioning system in the intermediate seasons using free-cooling or free-heating modes. These units, if installed on existing buildings, guarantee the energy requalification of the system through the management of the air change without additional charges; in the case of new installations, instead, the air change is completely carried out allowing to reduce the size of the main air conditioning system. In the intermediate seasons the building will benefit from free or partially-generated cooling from these units, which during the partial load phases allow the main system to operate with higher efficiency.

Show moreShow less

Certifications

foto applicazioni

Data Sheet

RXH/HE 010

  • Nominal airflow rate [m3/h]
    1000
  • Declared type of ventilation unit
    UVNR-B (Non Residential Ventilation Units - Bidirectional)
  • Type of drive installed
    Analog signal on EC fan (0-10Vdc)
  • Type of fans [type/nr.]
    EC/2
  • Type of heat recovery system HRS [type/nr.]
    static counter-flow / 1
  • Winter Thermal Efficiency ηt_nrvu [%]
    75,2
  • Winter Thermal Efficiency [%]
    83,7
  • Nominal electrical power consumption [kW]
    0,54
  • Max electrical power absorbed [kW]
    0,68
  • Max electrical current absorbed [A]
    2,80
  • SFPint [W/m3/s]
    858
  • SFPlim 2018 [W/m3/s]
    1121
  • External nominal pressure Δps, ext [Pa]
    250
  • Internal pressure drop Δps, [Pa]
    290
  • Fans static efficiency (UE) n.327/2011 [%]
    58,0
  • Max. external leakage percentage [%]
    max 3,5 % at -400 Pa
  • Max. internal leakage percentage [%]
    max 5,0 % at +250 Pa
  • Energy classification filters
    ePM1 55% (F7) | ePM1 55% (F7)
  • Filter pressure switch
    present
  • Sound power level [dBA]
    62
  • Sound pressure level [dBA]
    45
  • Power supply [V/ph/Hz]
    230/1/50
dimensional drawing
  • Dimension L (mm)
    2310
  • Dimension W (mm)
    810
  • Dimension H (mm)
    1080
  • Weight (kg)
    268
configuration H1
configuration H2
Sei Interessato?
If you are interested in this product, please contact us or find your nearest sales agency.
DOCUMENTATION
All the documentation related to this product is at your disposal: price list, information booklet and connection diagram.

Accessories

Discover the accessories dedicated to this specific product

ePM10 50% (G4) air pre-filter
ePM10 50% (G4) air pre-filter
Electric re-heating battery
Electric re-heating battery
3 way modulating valve
3 way modulating valve
Hot water coil
Hot water coil
Cold water coil
Cold water coil
Defrost system for TEMPERATE CLIMATES (down to -5°C external)
Defrost system for TEMPERATE CLIMATES (down to -5°C external)
Defrost system for SEVERE CLIMATES (down to -15°C external)
Defrost system for SEVERE CLIMATES (down to -15°C external)
Air damper with actuator
Air damper with actuator
Flexible joints kit (4 pcs)
Flexible joints kit (4 pcs)
ePM1 55% (F7) rigid bag filter
ePM1 55% (F7) rigid bag filter
ePM10 60% (M5) rigid bag filter
ePM10 60% (M5) rigid bag filter
ePM1 80% (F9) rigid bag filter
ePM1 80% (F9) rigid bag filter
Ethernet port and TCP/IP modbus | BACnet port
Ethernet port and TCP/IP modbus | BACnet port
Second remotable control panel with LCD display
Second remotable control panel with LCD display