Description

Any occupied room requires the correct supply of fresh air and, at the same time, the control of the internal thermo-hygrometric conditions, through the recovery of energy from the air extracted from the room, by means of rotary wheel heat recovery, the level of well-being of the occupants is guaranteed, both in summer and winter. For buildings that require air changes and are not equipped with dedicated air conditioning systems, the installation of such units allows the supply of primary air at controlled temperature without substantially changing the internal conditions in the occupied spaces. These units also make it possible to guarantee support for the air conditioning system in the intermediate seasons using free-cooling or free-heating modes. These units, if installed on existing buildings, guarantee the energy requalification of the system through the management of the air change without additional charges; in the case of new installations, instead, the air change is completely carried out allowing to reduce the size of the main air conditioning system. In the intermediate seasons the building will benefit from free or partially-generated cooling from these units, which during the partial load phases allow the main system to operate with higher efficiency.

Show moreShow less

Certifications

foto applicazioni

Data Sheet

RWH/HE 010

  • Declared type of ventilation unit
    UVNR-B (Non Residential Ventilation Units - Bidirectional)
  • Type of drive installed
    analog signal on EC fan (0-10Vdc)
  • Type of fans [type/nr.]
    EC/2
  • Type of heat recovery system HRS [type/nr.]
    static counter-flow / 1
  • Winter Thermal Efficiency ηt_nrvu [%]
    82,6
  • Winter Thermal Efficiency [%]
    82,1
  • Nominal airflow rate [m3/h]
    1000
  • Electrical power consumption [kW]
    0,45
  • Installed electrical power [kW]
    1,16
  • SFPint [W/m3/s]
    751
  • SFPlim 2018 [W/m3/s]
    1345
  • Front speed at design range [m/s]
    1,5
  • External nominal pressure Δps, ext [Pa]
    250
  • Internal pressure drop Δps, int Supp./Ret. [Pa]
    215 | 202
  • Fans static efficiency (UE) n.327/2011 [%]
    55,5
  • External leakage class
    L1
  • Max. internal leakage percentage [%]
    max 5,0 % at +250 Pa
  • Energy classification filters
    ePM1 55% (F7) | ePM10 60% (M5)
  • Filter pressure switch
    present
  • Sound power level [dBA]
    65
  • Sound pressure level [dBA]
    49
  • Power supply [V/ph/Hz]
    230/1/50
  • [50 mm PROFILE MONOBLOCK]
  • Dimension L (mm)
    2360
  • Dimension W (mm)
    750
  • Dimension H (mm)
    1070
  • Weight (kg)
    282
  • [60 mm PROFILE MONOBLOCK]
  • Dimension L (mm)
    2380
  • Dimension W (mm)
    770
  • Dimension H (mm)
    1090
  • Weight (kg)
    285
Sei Interessato?
If you are interested in this product, please contact us or find your nearest sales agency.